XMT温控仪显示温度与实际温度有偏差怎么调?我的想法对吗?
拿pt100来说.
0100.00
1100.39
50119.40
100138.51
150157.33
200175.86
250194.10
300212.05
350229.72
400247.09
450264.18
500280.98
如果数显表显示200度,实际温度250度,是不是pt100串联个电阻使175.86变成194.10欧姆就好了?
知道市面上现在的温控仪温度是可调的,但是老设备上面的是不能调的,温度不准了,想弄成能够调节的.

XMT温控仪显示温度与实际温度有偏差怎么调?我的想法对吗?拿pt100来说.0100.001100.3950119.40100138.51150157.33200175.86250194.10300212.05350229.72400247.09450264.18500280.98如果数显表显示200度,实际温度250
如果在对准度要求不是很高的场合可以用此方法.只是PT100的阻值随温度变化量不是恒定的,而是有一个变化曲线,仪表是通过软件计算将这一曲线值在显示端显示出来,比较准确.老式的温控仪内部肯定也有调温的电位器,将PT100放在烧开的开水中,调电位器到100度,那个电位器咨询厂家!